Hitachi Air Conditioners Australia
Total Indoor Comfort Solutions !


PACKAGED AIR CONDITIONERS

Reverse Cycle Ducted Air Conditioning Systems

SPECIFICATIONS


SINGLE PHASE MODELS

  MODELS

LD-2.5LM5/
RAS-2.5HQVE5

LD-3LM5/
RAS-3HQVE5

LD-4LM5/
RAS-4HQVE5

  CAPACITY
  Total Cooling Capacity *

6.8

8.6

12.7

  Total Heating Capacity #

7.6

9.1

13.2

  INDOOR UNIT
  Model Name

LD-2.5LM5

LD-3LM5

LD-4LM5

  External Finish

Galvanised Sheet

  Power Supply

Single Phase, 50Hz, 220-240V

  Controls

Hitachi Utopia 5 Series LCD Remote Control

  Air Flow l/s

450

540

720

  Dimensions
(Excluding Spiggots)
H(mm)
W(mm)
D(mm)

387
852
500

387
852
500

418
978
544

  Weight kgs

37

37

47

  Spiggots Return Air
Supply Air

315 x 710
260 x 500

315 x 710
260 x 500

340 x 850
305 x 710

  OUTDOOR UNIT
  Model Name

RAS-2.5HQVE5

RAS-3HQVE5

RAS-4HQVE5

  External Finish

Synthetic Resin Paint Baked on Galvanised Steel
Munsell 2.5Y 8/2 Beige

  Power Supply

Single Phase, 50Hz, 220-240V

  Running Current (Amps)

9.6

14.3

22.9

  Maximum Unit Current (Amps)

20.5

20

25

  Sound Pressure Level dB(A)

51

52

53

  Dimensions H(mm)
W(mm)
D(mm)

735
890
285

885
890
285

1135
890
285

  Weight kgs

63

73

87

  PIPING
  Connection Type

Flared Connections Standard

  Size O.D Liquid (mm)

9.53(3/8)

9.53(3/8)

9.53(3/8)

  Size O.D Gas (mm)

15.88(5/8)

15.88(5/8)

19.05(3/4)




OPERATING RANGE

  COOLING & HEATING CONDITIONS Cooling Heating
  Outdoor Air Temperature (Max.) 43oC Db 21oC Db
    (Min.) -10oC Wb -7oC Wb

* Rated at 27 C Db / 19.5 C Wb Entering Air, 35 C Ambient
# Rated at 21 C Db Entering Air, 7 C Db / 6 C Wb Ambient. Heating Capacity indicates the actual heating capacity excluding frost on the heat exchanger and defrosting operation.
Design and specifications are subject to change with product improvement.