floor waste collar

Floor wastes in wet areas are notoriously difficult to seal in the event of a fire. The lack of a pipe stack above the floor level means that the floor grate offers little protection from fire and smoke once the pipe work has burnt through. AS4072: Part 1 demands that the fire resistance test of floor wastes must be conducted on pipe work that is identical to the installed configuration.

PromaSnap® Floor Waste System has been tested for floor waste applications to AS1530: Part 4 and AS4072: Part 1 for 120 minutes with uPVC pipe and fittings. PromaSnap® Floor Waste System has been designed to not only provide a tested system but also provide an effective, simple solution for water proofing and the levelling of the screed for tiling and water flow from the floor.

The system consists of a PROMASEAL® PipeSeal to hold pipe work in place. If the slab depth is over 125mm deep, the length of pipe required is 75mm less than the slab thickness, e.g. for a 300mm slab depth a 225mm length of pipe is required.

For slabs less than 125mm thick, reduce the length of the spigot on the PromaSnap® Floor Waste System that connects to the pipe. To ensure the puddle flange is level, it may be prudent to cut the pipes slightly less than this 75mm.

PromaSnap® Floor Waste System is manufactured entirely from recycled and recyclable material and is certified under the WaterMark Certification Scheme.